Sounder Base

FW2509 - Intelligent Notification Base

Local Audible Alarm • Addressable Technology • Detector Compatible

INTELLIGENT NOTIFICATION DEVICE
FW2509 Sounder Base
FW2509 Front View
UL/ULC Listed Intelligent Addressable

Sounder Base

FW2509

UL/ULC Listed
85dB @ 10ft
Addressable Loop
-10°C to +50°C
15-28 VDC
Intelligent Circuit

The FW2509 Sounder Base is an intelligent addressable device designed for use with Maple Armor smoke, heat, and multisensor detectors. It provides localized audible alarm notification (85dB minimum), ideal for multi-room applications such as hotels, apartments, and commercial buildings, ensuring maximum safety through precise notification.

Technical Specifications

Model NumberFW2509
Product NameSounder Base
CategoryFire Notification / Sounder Base
CertificationUL 464, UL 268, CAN/ULC-S525
ManufacturerMaple Armor / Tongfang BMS
Operating Voltage15 to 28 VDC
Standby Current≤ 0.1 mA
Alarm Current≤ 35 mA (Max)
Sound Level≥ 85 dB @ 10 ft (3 m)
Operating Temperature-10°C to +50°C (14°F to 122°F)
Operating Humidity0% to 95% RH (Non-condensing)
Mounting4" Square Box / Octagonal Box
CompatibilityMaple Armor Smoke, Heat, Multisensor Detectors
WarrantyStandard 3-Year Warranty
Sound Output Visualization (85dB @ 10ft)

Audible alarm pattern - 85dB minimum output at 10 feet

Product Overview

The FW2509 Sounder Base integrates both detection and notification functions into a single compact unit. Designed for efficiency and reliability, it provides localized audible alarm capabilities while maintaining compatibility with the complete Maple Armor detection system.

Intelligent Addressing

Electronically addressable via fire alarm control panel for easy configuration.

Built-in Synchronization

Multiple sounder bases on the same SLC loop can be synchronized.

Low Power Design

Minimal standby current consumption (<0.1 mA) for energy efficiency.

Typical Applications
Hospitality
Hotels, motels, resorts
Commercial Offices
Multi-tenant buildings
Residential
Apartments, condos
Healthcare
Assisted living facilities

Product Features

Electrical Features
  • Operating Voltage: 15-28 VDC
  • Standby Current: ≤0.1 mA
  • Alarm Current: ≤35 mA (Max)
  • Sound Output: ≥85dB @ 10ft
  • Electronic addressing via controller
Mechanical Features
  • Compact design for easy installation
  • Compatible with 4" square/octagonal boxes
  • Visual LED indicator for alarm status
  • Screw terminal connections
  • Operating temp: -10°C to +50°C

Installation & Configuration

4" Square Box
Standard electrical box mounting
Octagonal Box
Ceiling mounting configuration
Direct Mount
Surface mounting with backbox
Installation Steps
  1. Mount backbox securely to ceiling or wall
  2. Connect SLC loop wires to terminal block
  3. Set device address via control panel (electronic addressing)
  4. Secure sounder base to backbox with mounting screws
  5. Install compatible detector head into base
  6. Test operation and verify communication with panel
  7. Confirm sound output meets requirements

Compatibility & Applications

Compatible Detectors
  • FW2801 Photoelectric Smoke Detector
  • FW2802 Heat Detector
  • FW2803 Multisensor Detector
  • FW2804 Photoelectric w/ Heat
Compatible Panels
  • Maple Armor FW2000 Series
  • Maple Armor FW2100 Series
  • Maple Armor FW2200 Series
System Integration: The FW2509 Sounder Base provides localized notification while maintaining full addressable communication with the fire alarm control panel, allowing for precise identification of alarm locations.